电网技术 2009, 33(15) 54-59 DOI:     ISSN: 1000-3673 CN: 11-2410/TM

本期目录 | 下期目录 | 过刊浏览 | 高级检索                                                            [打印本页]   [关闭]
特高压工程建设与环境
扩展功能
本文信息
Supporting info
PDF(316KB)
[HTML全文]
参考文献[PDF]
参考文献
服务与反馈
把本文推荐给朋友
加入我的书架
加入引用管理器
引用本文
Email Alert
文章反馈
浏览反馈信息
本文关键词相关文章
计算;混合电场;同走廊;输电线路
本文作者相关文章
PubMed
交流线路与±800 kV直流线路同走廊时的地面混合电场研究
杨勇,陆家榆,鞠勇
中国电力科学研究院,北京市 海淀区 100192
摘要

交流线路与 ±800 kV直流线路共用走廊的情况将在我国出现,因此需要研究该种线路地面混合电场的计算方法,以满足工程设计和环境保护需要。在分析同走廊架设的交流线路与±800 kV直流线路相互影响的基础上,提出了一种计算该类线路地面混合电场的方法。通过对比使用该方法得到的计算结果与不考虑两种线路相互影响时的计算结果,得到如下结论:相对于忽略交直流线路的相互影响,当考虑其相互影响时,在同走廊交直流线路中心附近,地面混合电场的瞬时最大值横向分布有波动;两种计算方法得到的地面混合电场有效值分布曲线基本重合;在一个交流周期内,同走廊线路地面混合电场的最大值与单独 ±800 kV直流线路地面合成电场的最大值差别很小。

关键词 计算;混合电场;同走廊;输电线路  
Study on the Hybrid Electric Field Over the Ground Surface Under AC Lines and ±800 kV DC Lines in the Same Corridor
YANG Yong ,LU Jia-yu ,JU Yong
China Electric Power Research Institute,Haidian District,Beijing 100192,China
Abstract:

Parallel adjacent erection of AC transmission lines and ±800 kV DC transmission lines in the same corridor will occur in China, so the calculation method for the hybrid electric field over the ground under this type of lines should be studied so as to satisfy the requirements of engineering design and environmental protection. Based on the analysis of mutual influences between AC transmission lines and ±800 kV DC transmission lines in the same corridor, a calculation method is proposed. Through the comparison between the calculation results achieved with this method and the corresponding calculation results obtained when the mutual influences between AC transmission lines and ±800 kV DC transmission lines are neglected, some conclusions can be drawn as follows: compared with the calculation results obtained when the mutual influences are neglected, near the center of AC transmission lines and ±800 kV DC transmission lines in the same corridor, the lateral distribution of the instantaneous maximal values of the hybrid electric field obtained with the proposed method fluctuates; the lateral distributions of the virtual values of the hybrid electric field obtained respectively with the two different calculation methods almost overlap completely; the difference between the maximal value of the hybrid electric field in an AC cycle under this type of lines and the maximal value of DC electric field in the presence of space charge produced by single ±800 kV DC transmission lines is very small.

Keywords: calculation;hybrid electric field;same corridor;transmission lines  
收稿日期 2009-05-22 修回日期 2009-05-24 网络版发布日期 2009-08-13 
DOI:
基金项目:

通讯作者: 杨勇
作者简介:
作者Email:

参考文献:
本刊中的类似文章

Copyright by 电网技术